HPDJ-DGA Transformer Oil Chromatography On-line Monitoring System

HPDJ-DGA Transformer Oil Chromatography On-line Monitoring System
BASIC INFO

HPDJ-DGA Transformer Oil Chromatography On-line Monitoring System


General Information

HPDJ-DGA Transformer Oil Gas Analyzer is an online monitoring device for dissolved gas in transformer oil based on gas chromatography technology. Potential fault are determined, release alert as per preset value through expert diagnosis system.

The device adopts distributed control sampling technology and has self-diagnosis and self-recovery functions. Each function module is weak coupling, function independent, adopting rack structure, easy for engineering maintenance.


Fetures


Maintenance-free, no need to replace gas cylinder.


On-line detection the concentration and growth rate of H2, CO, CO2, CH4, C2H4, C2H2, C2H6.


Modular design and compact structure, easy for maintenance, with high expansibility, can be easily integrated to other monitoring equipment.


Quantitative cleaning cycle sampling mode, to reflect the state of dissolved gas in transformer oil.


Pumpless vacuum degassing technology, no need vacuum pump and improve reliability and stability of system.


Special complex chromatographic column, to improve the separation degree of the gas composition.


Special linear detector, monitoring data is real and reliable, test results are very close to the laboratory data.


Independent unit within chassis to control temperature and humidity, to remove regional and seasonal influence.


With high data acquisition precision, it adopts △-ε 24-digit ADC and digital filter. It uses auto calibration to collect spectrogram.


With various data display and query modes, report and trend graph. Historical data can be saved up to 10 years.


Strong environmental adaptability, successful application in the cold, high temperature, high humidity, high altitude area.


Strong anti-interference ability, electromagnetic compatibility can satisfy the relevant standard.


With two levels of alarm function, the alarm signal can be far transmitted.


Faster analysis cycle, minimum monitoring cycle is 40 minutes, can be set by users.


Complete oil return technology, during the degassing process, oil sample does not contact the chromatogram carrier gas, the use of various means of control, to ensure that the return transformer body of the oil sample fully meet the requirements.


Strengthened system diagnosis system, results are given through improved three-ratio method, David triangle method and cube diagram method.


With various communication methods to transfer data, RS485, IEC61850, GPRS wireless transfer and short message are applied to transfer data.


Support Ethernet/optical connection, data transfer, device control and parameter setting with fully digitalization and remote control.


Oil/gas auto calibration and auto cleaning functions are available.


Specification

Environmental temperature

-40℃+70℃

Environmental humidity

Relative humidity 5-95%(no condensation)

Atmospheric Pressure

80kPa-110kPa

Power supply

AC 220V±10%, 50Hz

Monitoring components

H2, CO, CO2, CH4, C2H4, C2H2, C2H6, H2O, growth rate and concentration

Analysis and diagnostic function

Analyze and diagnose monitoring data by three-ratio method, David triangle method and cube diagram method. Original spectrogram can be supplied.

Min. Detection cycle

40-60mins, user-defined, default four times a day.

Sampling mode

Cycling sampling, to reflect real-time situation of inside gas.

Separating mode of oil and gas

Vacuum degassing mode, degassing for three times continuously.

Data storage lifespan

≥ 10 years

Carrier gas quantity

Self-made carrier gas, not interrupted all year round. No need to replace gas cylinder.

Monitoring gas

Measuring range

Min. detection

Error

H2

2- 2000 ppm

1 ppm

±10%

CO

5- 20000 ppm

5 ppm

±10%

CH4

0.2- 2000 ppm

0.2 ppm

±10%

C2H4

0.2- 2000 ppm

0.2 ppm

±10%

C2H6

0.2- 2000 ppm

0.2 ppm

±10%

C2H2

0.2- 2000 ppm

0.2 ppm

±10%

CO2

25- 20000 ppm

25 ppm

±10%

H2O

1 - 800 ppm

Oil temperature

-40℃~200℃

Total air quantity

0.2-15%

Total hydrocarbon

1 - 8000 ppm

Stability (measurement error)

At the same testing condition, error is no more than 10% for the same oil sample. (medium concentration)

IP class

IP66




Use conditions 


Altitude

≤3000m

Ambient temperature

-10℃~+45℃(indoors); -40℃~+70℃(outdoors)

Max. daily temperature difference

25℃

Max. relative humidity

95% (daily average); 90% (monthly average)

Air pressure

86kPa~106kPa

Anti-shock ability

Horizontal acceleration 0.30g; vertical acceleration 0.15g

Installation environment  

Indoor installation. The room shall be equipped with air-conditioner, no shielding, without anti-static measures.



Rated parameters


Rated power supply (AC)

220V/100V, permissible error ±20% (harmonics), total voltage distortion rate ≤8%.

Rated power supply (DC)

220V/110V, permissible variation range ±20%.

Rated AC voltage

 

57.7V/100V/220V, overload capacity is 1.2times of rated voltage, peak coefficient ≥2.

Rated AC current

1A/5A, overload capacity is 1.2 times of rated current, continuously working, peak coefficient ≥3.

Rated frequency

50Hz, permissible error -5%~+5%.




Power supply


The power supply of the substation condition monitoring system should be safe and reliable, and the station control layer equipment should be powered by 220VAC Uninterrupted Power Supply (UPS). Each monitoring unit in the process layer is powered by 220V AC system.


Lightning protection, grounding, anti-interference


The substation condition monitoring system shall have protective measures against over-voltage.

There is no separate grounding grid for the condition monitoring system. According to the principle of "one-point grounding", the ground wire is connected to one point of the main grounding grid of the substation.

Over-voltage protection device shall be installed on 220V AC power supply, communication line and the leading end of the grounding network, and the protection device parameters shall conform to the insulation performance index of the equipment.

The chassis, cabinet and cable shielding layer of the condition monitoring system should be grounded reliably. The connection between the process layers of the condition monitoring system, the connection between the process layer and the station control layer, and the connection between the communication ports of the equipment shall be isolated.

The device is installed in a room without electromagnetic shielding. The device itself should meet the requirements of anti-electromagnetic field interference and electrostatic influence. In case of lightning overvoltage, operating overvoltage and short-circuit fault of the primary equipment, the equipment shall not mal-operate, and all equipment shall meet the following anti-interference requirements:

1) For electrostatic discharge, it conforms to GB/T 17626-4-2 class 4.

2) For the radiation electromagnetic field, it conforms to the GB/T 17626-4-3 class 3.

3) For fast transient, it conforms to GB/T 17626-4-4 class 4.

4) For surge, it conforms to GB/T 17626-4-5 class 3.

5) For conduction of electromagnetic induction, it conforms to GB/T 17626-4-6 class 3.

6) For power frequency electromagnetic field, it conforms to GB/T 17626-4-8 class 4.

7) For the pulse electromagnetic field, it conforms to GB/T 17626-4-9 class 5.

8) For damped oscillating magnetic field, it conforms to GB/T 17626-4-10 class 5.

9) For oscillating waves, it conforms to GB/T 17626-4-12 class 2 (signal port).



Accessories


No.

Equipment Name

Specifications

Qty

Remark

1

Transformer Oil Gas Online monitoring system

535*600*1100

1

 

2

Flange

Based on the port of transformer

2

 

3

Stainless steel tube

Φ6*30M

1

 

4

Optical fiber

Multimode 4-core, 200M

1

 

5

Terminal box

 

2

 

6

Jumper

SC-SC

2

 

7

Fiber converter

multimode

1

 

8

Ethernet cable

0.5M

2

 

9

Screw

M12*1.25M, Φ6

2

 

10

Expansion screw

M10*100

4

 

11

Cabinet key

2pcs

1

 

12

Cable card

4pcs+several nylon cable ties 

1

 

13

Stainless steel tube

Φ3*2M

1

 

14

Insulation Pipe and other components

Insulation pipe Φ6*2M 4pcs, Au tape 50*25M 1roll, stainless steel hoop 8*32 2pcs

1

 


We can customized,  welcome to consult with us!

 

Company Profile

HONOPOWER DEVELOPMENT Co., Ltd. is a professional manufacturer specialized in electrical safety testing equipment, especially high voltage testing equipment.

 

We had researched and produced and sell test equipment for over ten years,our products have been sold well nationwide and worldwide.

 

Our test equipment can test for various kinds of products, such as SF6 Gas, GIS Systems,Transformers,Generators, Circuit Breakers, Relays, Surge Arresters, Insulators, Cables, Casings and CT/ PTs, etc.

 

Contact Us

HONOPOWER DEVELOPMENT Co., Ltd.

Email/Skype:sales06@hvhipot.com

Mobile/Whatsapp+86 13135657923

Tel+86-27-85568138

Add 10-B7, JinYinTan Modern Enterprise City, Dongxihu District, Wuhan, China